§ 111.97-9 Overcurrent protection.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 111.97-9, § 111.97-9 Overcurrent protection, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227161
Permanent ID
ys:prov:227161@1
SHA-256
fe906dc5164ca2c88f11bf25d0be73fcb890240fe33aadb07940d4cdbefa2335

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Overcurrent devices must be arranged to isolate a fault with as little disruption of the system as possible. The relationship between the load and the rating or setting of overcurrent devices must meet the following: (a) The rating or setting of each feeder overcurrent device must be not less than 200 percent of its maximum load. (b) The rating or setting of a branch circuit overcurrent device must be not more than 25 percent of that of the feeder overcurrent device.