46 CFR 111.101-3
§ 111.101-3 General requirements.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.101-3, § 111.101-3 General requirements, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227168
- Permanent ID
ys:prov:227168@1- SHA-256
321a1fba17a3746cbaa35002e3ed533a3b56910001eb8e19d4ebf96fc81ab56f
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each electric motor driving a submersible bilge pump must be in an open end air bell of rugged construction and be of a size that does not allow water to enter the motor if the compartment that the motor is in is flooded to the uppermost continuous deck.
(b) The motor, if of the open type, must be protected from splashing water from the bottom.
(c) The cable to each motor must enter through the open bottom of the air bell.
(d) Each motor must be able to operate continuously at rated load under any condition, dry or with water in the air bell at any level up to the maximum allowed under paragraph (a) of this section.
(e) Each motor controller must be above the uppermost continuous deck. There must be a master switch at the controller and a master switch at the motor. The master switch at the motor must be disconnected from the circuit when the motor is started or stopped from the master switch at the controller.
(f) Each motor must be energized from the final emergency power source.