46 CFR 111.105-40

§ 111.105-40 Additional requirements for RO/RO vessels.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 111.105-40, § 111.105-40 Additional requirements for RO/RO vessels, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227194
Permanent ID
ys:prov:227194@1
SHA-256
f443747baa1a19359dcbf8914a1f83860cae56b8a4d67bad8b07945e1aed98e4

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Each RO/RO vessel must meet ABS Marine Vessel Rules (incorporated by reference; see 46 CFR 110.10-1), section 4-8-4/27.3.2. (b) Each item of installed electrical equipment must meet the requirements for a Class I, Division 1; Class I, Division 2; Zone 0; Zone 1; or Zone 2 hazardous location when installed 460 mm (18 inches) or more above the deck of closed cargo spaces. Electrical equipment installed within 460 mm (18 inches) of the deck must be suitable for either a Class I, Division 1; Zone 0; or Zone 1 hazardous location. (c) Where the ventilation requirement of ABS Marine Vessel Rules section 4-8-4/27.3.2 is not met— (1) All installed electrical equipment must be suitable for a Class I, Division 1; Zone 0; or Zone 1 hazardous location; or (2) If fitted with an approved fixed gas detection system (set at 25 percent of the LEL), each item of installed electrical equipment must meet the requirements for either a Class I, Division 1; Class I, Division 2; Zone 0; Zone 1; or Zone 2 hazardous location.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.