§ 111.106-5 Cable and wiring.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.106-5, § 111.106-5 Cable and wiring, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227202
- Permanent ID
ys:prov:227202@1- SHA-256
4327ef5af22bbfb387e29c561d4f187186e38a7cc2b6a00354b0c379b1478b9a
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Cable and wiring in hazardous locations must meet the cable construction and testing provisions of IEEE 1580; ANSI/UL 1309; MIL-DTL-24640C; MIL-DTL-24643C; or 60092-350:2014 and IEC 60092-353:2016 (incorporated by reference, see § 110.10-1), including the respective flammability tests contained therein, and must be of a copper-stranded type.
(b) Type MC cables, when used, must meet the requirements in § 111.60-23 of this part.
(c) For intrinsically safe systems under the standards cited in § 111.106-3(b)(1) and (b)(2) of this subpart, the wiring methods must meet Section 504.30 of NFPA 70 (incorporated by reference, see § 110.10-1). For intrinsically safe systems under the standards cited in § 111.106-3(b)(3) of this subpart, the installation and wiring must meet Clause 7, except for Clause 7.3.1, of IEC 60092-502:1999 (incorporated by reference, see § 110.10-1).