§ 112.05-3 Main-emergency bus-tie.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 112.05-3, § 112.05-3 Main-emergency bus-tie, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227224
Permanent ID
ys:prov:227224@1
SHA-256
51ea3d7b376edae0362ad5ebb9ca17e35b4df9d3b16f7f823fac88188365e178

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Each bus-tie between a main switchboard and an emergency switchboard must: (a) Disconnect automatically upon loss of potential at the emergency switchboard; (b) Be arranged to prevent parallel operation of an emergency power source with any other source of electric power, except for interlock systems for momentary transfer of loads; and (c) If arranged for feedback operation, open automatically upon overload of the emergency power source before the emergency power source is tripped off the line from the overload.