46 CFR 112.20-15
§ 112.20-15 Transfer of emergency loads.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 112.20-15, § 112.20-15 Transfer of emergency loads, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227236
- Permanent ID
ys:prov:227236@1- SHA-256
f18c3fada3d040ac5be85644c7edd72b44d44a7aa71bed315d5724f3828c6e95
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) When the potential of the final emergency power source reaches 85 to 95 percent of normal value, the emergency loads under § 112.15-5 must transfer automatically to the final emergency power source and, on a passenger vessel, this transfer must be accomplished in no more than 45 seconds after failure of the normal source of power.
(b) When the potential from the normal source has been restored, the emergency loads must be manually or automatically transferred to the normal source, and the final emergency power source must be manually or automatically stopped.
(c) If the potential of the final emergency power source is less than 75 to 85 percent of normal value while supplying the emergency loads, the temporary emergency loads under § 112.15-1 must transfer automatically to the temporary emergency power source.