46 CFR 112.25-10
§ 112.25-10 Transfer of emergency loads.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 112.25-10, § 112.25-10 Transfer of emergency loads, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227241
- Permanent ID
ys:prov:227241@1- SHA-256
02b93fb076602079bcfec1184c3eafa1a2d050e50806d31a9d991cd12e36e097
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) When the potential of the final emergency source reaches 85 to 95 percent of normal value, the emergency loads under § 112.15-5 must transfer automatically to the final emergency power source and this transfer must be accomplished in no more than 45 seconds after failure of the normal source of power.
(b) When the potential from the normal source has been restored, the emergency loads must be manually or automatically transferred to the normal source, and the final emergency power source must be manually or automatically stopped.