§ 112.43-15 Emergency lighting feeders.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 112.43-15, § 112.43-15 Emergency lighting feeders, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227266
- Permanent ID
ys:prov:227266@1- SHA-256
bd1a917fecbbcc87a1383291112af9724d9504eda308dd30dbfbdd60a1e4659e
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
For a vessel with fire bulkheads forming fire zones, at least one emergency lighting feeder must supply only the emergency lights between two adjacent main vertical fire zone bulkheads. The emergency lighting feeder must be separated as widely as practicable from any general lighting feeder supplying the same space.