§ 113.10-9 Power supply.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 113.10-9, § 113.10-9 Power supply, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227288
Permanent ID
ys:prov:227288@1
SHA-256
fb488d592c4b1a8744de78d8b5ed3143c244a78a659847cb81e0f3787e8617c1

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) General. There must be at least two sources of power for the electrical equipment of each fire detecting and alarm system. The normal source must be the main power source. The other source must be the emergency power source or an automatically charged battery. If the other source is an automatically charged battery, the charger must be supplied from the final emergency power source. Upon loss of power to the system from the normal source, the system must be automatically supplied from the other source. (b) Batteries. Each battery used in a fire detecting and alarm system must meet Subpart 111.15 of this chapter. (c) Capacity of power supply branch circuit. The capacity of each branch circuit providing power to a fire detection or alarm system must not be less than 125 percent of the maximum load.