46 CFR 120.372

§ 120.372 Equipment and conductor grounding.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 120.372, § 120.372 Equipment and conductor grounding, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227597
Permanent ID
ys:prov:227597@1
SHA-256
1bca11a3fd9485216bce6706fcc1cb0f595bb5355aae562b0578ecb3c0a185a7

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) All metallic enclosures and frames of electrical equipment must be permanently grounded to the hull on a metallic vessel. On a nonmetallic vessel, the enclosures and frames of electrical equipment must be bonded together to a common ground by a normally non-current carrying conductor. Metallic cases of instruments and secondary windings of instrument transformers must be grounded. (b) On a nonmetallic vessel, where a ground plate is provided for radio equipment, it must be connected to the common ground. (c) Equipment grounding conductors must be sized in accordance with Section 250-95 of the NEC (NFPA 70), or other standard specified by the Commandant. (d) Each insulated grounding conductor of a cable must be identified by one of the following means. (1) A green braid or green insulation; (2) Stripping the insulation from the entire exposed length of the grounding conductor; or (3) Marking the exposed insulation of the grounding conductor with green tape or green adhesive labels. (e) Cable armor must not be used to ground electrical equipment of systems.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.