§ 120.390 Shore power.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 120.390, § 120.390 Shore power, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227601
- Permanent ID
ys:prov:227601@1- SHA-256
6e23d519727c729a19726859de82db957c548629eb053e8a34db3ed9ec0151da
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
A vessel with an electrical system operating at more than 50 volts, which is provided with a means to connect to shore power, must meet the following:
(a) A shore power connection box or receptacle must be permanently installed at a convenient location:
(b) A cable connecting the shore power connection box or receptacle to the switchboard or main distribution panel must be permanently installed;
(c) A circuit breaker must be provided at the switchboard or main distribution panel for the shore power connection; and
(d) The circuit breaker, required by paragraph (c) of this section, must be interlocked with the vessel's power sources so that shore power and the vessel's power sources may not be operated simultaneously.