§ 129.390 Shore power.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 129.390, § 129.390 Shore power, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227844
Permanent ID
ys:prov:227844@1
SHA-256
2a1ce453f144dc66c0435af3207f535e9279525e2fa66fc8fa734b2c4267410a

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Each vessel that has an electrical system operating at more than 50 volts and has provisions for receiving shore power must meet the requirements of this section: (a) A shore-power-connection box or receptacle must be permanently installed at a convenient location. (b) A cable connecting the shore-power-connection box or receptacle to the switchboard or main distribution panel must be permanently installed. (c) A circuit breaker must be provided at the switchboard or main distribution panel for the shore-power connection. (d) The circuit breaker, required by paragraph (c) of this section, must be interlocked with the feeder circuit breakers for the vessel's power sources to preclude the vessel's power sources and shore power from energizing the vessel's switchboard simultaneously, except in cases where system devices permit safe momentary paralleling of OSV power with shore power.