46 CFR 130.230

§ 130.230 Protection from refrigerants.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 130.230, § 130.230 Protection from refrigerants, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227869
Permanent ID
ys:prov:227869@1
SHA-256
d4e63676608195c4f4ea45fad450559a86f32c93eadd49ce83c521b3691b3d6c

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) For each refrigeration system that exceeds 0.6 cubic meters (20 cubic feet) of storage capacity if using ammonia or other hazardous gas, or exceeds 28.3 cubic meters (1,000 cubic feet) of storage capacity if using a fluorocarbon, as a refrigerant, there must be available one pressure-demand, open-circuit, self-contained breathing apparatus, approved by the National Institute for Occupational Safety and Health (NIOSH) and having at a minimum a 30-minute air supply, and a full facepiece. (b) Each self-contained breathing apparatus must be stowed convenient to, but outside, the space containing the refrigeration equipment. (c) A complete recharge in the form of a spare charge must be carried for each self-contained breathing apparatus. The spare charge must be stowed with the equipment it is to reactivate. (d) The self-contained breathing apparatus in a fireman's outfit, if fitted, complies with this section.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.