yourstate.us
46 CFR 143.260

§ 143.260 Fuel shutoff requirements.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 143.260, § 143.260 Fuel shutoff requirements, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228245
Permanent ID
ys:prov:228245@1
SHA-256
742f0676fa3acf13e6b8d2b081424eba2d61ba8b11366d36e05b69e6e4019bc2

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) This section does not apply to an excepted towing vessel as defined in § 136.110 of this subchapter. (b) To stop the flow of fuel in the event of a fire or break in the fuel line, a remote fuel shutoff valve must be fitted on any fuel line that supplies fuel directly to a propulsion engine or generator prime mover. (c) The valve must be installed in the fuel piping directly outside of the fuel oil supply tank. (d) The valve must be operable from a safe place outside the space where the valve is installed. (e) Each remote valve control must be marked in clearly legible letters, at least 25 millimeters (1 inch) high, indicating the purpose of the valve and the way to operate it.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.