46 CFR 143.560
§ 143.560 Electrical distribution panels and switchboards.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 143.560, § 143.560 Electrical distribution panels and switchboards, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228264
- Permanent ID
ys:prov:228264@1- SHA-256
c13e9c21e9c48af91c39f12aca99548610d3ce8655c1d7385edc36b648e39ab2
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each distribution panel or switchboard on a towing vessel must be:
(1) In a location that is accessible, as dry as practicable, adequately ventilated, and protected from falling debris and dripping or splashing water; and
(2) Totally enclosed and of the dead-front type.
(b) Each switchboard accessible from the rear must be constructed to prevent a person's accidental contact with energized parts.
(c) Nonconductive mats or grating must be provided on the deck in front of each switchboard and, if it is accessible from the rear, on the deck behind the switchboard.
(d) Each un-insulated current-carrying part must be mounted on noncombustible, nonabsorbent, and high-dielectric insulating material.
(e) Equipment mounted on a door of an enclosure must be constructed or shielded so that a person will not come into accidental contact with energized parts.