yourstate.us
46 CFR 147.67

§ 147.67 Halocarbon fire extinguishing systems.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 147.67, § 147.67 Halocarbon fire extinguishing systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228346
Permanent ID
ys:prov:228346@1
SHA-256
feaa1b5ac31a33bb78bf7d0082a92b50dd34e38e7a77a164d44e08eb62df3b53

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Each halocarbon cylinder forming part of a clean agent fixed fire extinguishing system must be: (1) Retested at least once every 12 years and before recharging if it has been discharged and more than five years have elapsed since the last test; or (2) As an alternative, a cylinder conforming to the requirements of 49 CFR 180.209(g) may be given the complete external visual inspection in lieu of hydrostatic testing provided for by that section. (b) A halocarbon cylinder must be removed from service if it: (1) Leaks; (2) Is dented, bulging, severely corroded, or otherwise weakened; (3) Has lost more than 5 percent of its tare weight; or (4) Has been involved in a fire. (c) Flexible connections between cylinders and discharge piping for halocarbon fire extinguishing systems must be renewed or retested in accordance with section 7.3 of NFPA 2001 (incorporated by reference, see § 147.7).

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.