46 CFR 151.40-11

§ 151.40-11 Refrigeration systems.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 151.40-11, § 151.40-11 Refrigeration systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228560
Permanent ID
ys:prov:228560@1
SHA-256
74ccd7ddf9b041bc87891e2a5d5f2b1a6136b1335a88d6f4d4a409bb91af2972

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Boiloff systems. The venting of cargo boiloff to atmosphere shall not be used as a primary means of temperature or pressure control unless specifically authorized by the Commandant. (b) Vapor compression, tank refrigeration, and secondary refrigeration systems: The required cooling capacity of refrigeration systems shall be sufficient to maintain the cargo at design operating conditions with ambient temperature of 115 °F still air and 90 °F still water. The number and arrangement of compressors shall be such that the required cooling capacity of the system is maintained with one compressor inoperative. Portions of the system other than the compressors need not have standby capacity.