§ 153.351 Location of 4m vent discharges.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 153.351, § 153.351 Location of 4m vent discharges, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228673
Permanent ID
ys:prov:228673@1
SHA-256
51ecd1b7556be494d35d6d02ce3a27f9b32a83a1fc129ec9131e3d895793dfce

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Except as prescribed in § 153.353, a 4m venting system must discharge: (a) At least 4m (approx. 13.1 ft) above the higher of: (1) the weatherdeck; or (2) any walkway that is within a 4m (approx. 13.1 ft) horizontal radius from the vent discharge. (b) At least 10m (approx. 32.8 ft) from air intakes for, or openings into, accommodation or service spaces.