§ 153.353 High velocity vents.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 153.353, § 153.353 High velocity vents, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228675
- Permanent ID
ys:prov:228675@1- SHA-256
61edf4274af30a98b766bf3828362ebb89b1dcb9bee249c18522d5cc45bf0ef7
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
The discharge point of a B/3 or 4m venting system must be located at least 3m (approx. 10 ft) above the weatherdeck or walkway if:
(a) The discharge is a vertical, unimpeded jet;
(b) The jet has a minimum exit velocity of 30 m/sec (approx. 98.4 ft/sec); and
(c) The high velocity vent has been approved by Commandant (CG-ENG).