§ 154.1135 Pumps.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 154.1135, § 154.1135 Pumps, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/228986
Permanent ID
ys:prov:228986@1
SHA-256
f897e716370f76c95a0290418491ec2f945f000606db0eba0d7c69ca5e1681fd

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Water to the water spray system must be supplied by: (1) A pump that is only for the use of the system; (2) A fire pump; or (3) A pump specially approved by the Commandant (CG-OES). (b) Operation of a water spray system must not interfere with simultaneous operation of the fire main system at its required capacity. There must be a valved cross-connection between the two systems. (c) Except as allowed under paragraph (d) of this section, each pump for each water spray system must have the capacity to simultaneously supply all areas named in § 154.1110. (d) If the water spray system is divided into sections, the pump under paragraph (a) of this section must have the capacity to simultaneously supply the required discharge density under § 154.1115(a) for: (1) The areas in §§ 154.1110(f) through (h) and 154.1115(b); and (2) The largest section that includes the required protection under § 154.1110 (a), (b), and (c).