§ 169.667 Switchboards.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 169.667, § 169.667 Switchboards, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230241
- Permanent ID
ys:prov:230241@1- SHA-256
32e015d731e2efbe8bd2d3f8e705700f34a8d7a70076bbc225b09b94a8dc2bf8
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each switchboard must be in as dry a location as practicable, accessible, protected from inadvertent entry, and adequately ventilated. All uninsulated current carrying parts must be mounted on nonabsorbent, noncombustible, high dielectric insulating material.
(b) Each switchboard must be—
(1) Totally enclosed; and
(2) Of the dead front type.
(c) Each ungrounded conductor of a circuit must have at the point of attachment to the power source either—
(1) A Circuit breaker; or
(2) A switch and fuse.
(d) Each switch other than one mounted on a switchboard must be of the enclosed type.