§ 169.677 Equipment protection and enclosure.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 169.677, § 169.677 Equipment protection and enclosure, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230251
- Permanent ID
ys:prov:230251@1- SHA-256
20ccb9d09e0d0c4582ef91d4c94b1c5c02b327631d5011e93247ad3a05c41194
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Except as provided in this section, all electrical equipment including motors, generators, controllers, distribution panels, consoles, etc., must be at least dripproof and protected.
(b) Equipment mounted on a hinged door of an enclosure must be constructed or shielded so that no live parts of the door mounted equipment will be exposed to accidental contact by a person with the door open and the circuit energized.
(c) Any cabinet, panel, or box containing more than one source of potential in excess of 50 volts must be fitted with a sign warning personnel of this condition and identifying the circuits to be disconnected to remove all the potentials in excess of 50 volts.
(d) Each distribution panelboard must be enclosed.