§ 169.682 Distribution and circuit loads.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 169.682, § 169.682 Distribution and circuit loads, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230256
- Permanent ID
ys:prov:230256@1- SHA-256
507199e8f0610afa326cd2dcd504b1489509769df5cc6acc0627aa5609ebdc4d
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Except as provided in paragraph (b) of this section, the connected load on a lighting branch circuit must not exceed 80 percent of the rating of the overcurrent protective device, computed using the greater of—
(1) The lamp sizes to be installed; or
(2) 50 watts per outlet.
(b) Circuits supplying electrical discharge lamps must be computed using the ballast input current.
(c) The branch circuit cables for motor and lighting loads must be no smaller than No. 14 AWG.