46 CFR 169.684

§ 169.684 Overcurrent protection for motors and motor branch circuits.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 169.684, § 169.684 Overcurrent protection for motors and motor branch circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230258
Permanent ID
ys:prov:230258@1
SHA-256
248e26dcb163eefc58b584cfa8ebc438950b183f0d9c31cdf8209940629dbf6f

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Except as provided in paragraph (d) of this section, each motor must be provided with running protection against overcurrent. A protective device integral with the motor that is responsive to motor current or to both motor current and temperature may be used. (b) The motor branch circuit conductors, the motor control apparatus, and the motors must be protected against overcurrent due to short circuits or grounds with overcurrent devices. (c) The motor branch circuit overcurrent device must be capable of carrying the starting current of the motor. (d) Each manually started continuous duty motor, rated at one horsepower or less, that is within sight from the starter location, is considered as protected against overcurrent by the overcurrent device protecting the conductors of the branch circuit.