§ 170.265 Class 3 doors; required locations.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 170.265, § 170.265 Class 3 doors; required locations, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230373
Permanent ID
ys:prov:230373@1
SHA-256
ce040f4c6fd44623e1d751ae5bf092c851ccfa66d2fc5131267c335ef58dd072

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

The following doors must always be Class 3: (a) Doors in all locations not addressed in §§ 170.255 and 170.260. (b) Doors between coal bunkers below the bulkhead deck that must be opened at sea. (c) Doors into trunkways that pass through more than one main transverse watertight bulkhead if the door sills are less than 2.14 meters above the deepest load line. (d) Doors below a deck, the molded line of which, at its lowest point at side, is less than 2.14 meters (7 feet) above the deepest load line if— (1) The vessel is engaged on a short international voyage as defined in § 171.010 of this subchapter; and (2) The vessel is required by § 171.065 of this subchapter to have a factor of subdivision of 0.5 or less.