46 CFR 181.310

§ 181.310 Fire main and hydrants.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 181.310, § 181.310 Fire main and hydrants, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230781
Permanent ID
ys:prov:230781@1
SHA-256
375748acbe9ba5aa411b884a1a87dcd0704b809832882a4bc419b16a74731b10

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) A vessel that has a power driven fire pump must have a sufficient number of fire hydrants to reach any part of the vessel using a single length of firehose. (b) Piping, valves, and fittings in a fire main system must comply with subpart G, part 182, of this chapter. (c) Each fire hydrant must have a valve installed to allow the firehose to be removed while the fire main is under pressure. (d) Spanner wrenches must be provided where a 40 millimeter (1.5 inch) diameter firehose is required by § 181.320(b). Existing vessels as of July 22, 2016 have 180 days to comply with this requirement.