yourstate.us
46 CFR 181.420

§ 181.420 Pre-engineered fixed gas fire extinguishing systems.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 181.420, § 181.420 Pre-engineered fixed gas fire extinguishing systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/230787
Permanent ID
ys:prov:230787@1
SHA-256
1c87ad7fe8c7595e6cdbe911c1277c0b752de0f30eefbbe5f02d9352266e65fb

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) A pre-engineered fixed gas fire extinguishing system must: (1) Be approved by the Commandant; (2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector; (3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space; and (4) Be installed in accordance with the manufacturer's instructions. (b) A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station: (1) A light to indicate discharge; (2) An audible alarm that sounds upon discharge; and (3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section. (c) Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.