49 CFR 192.357
§ 192.357 Customer meters and regulators: Installation.
United States · 49 CFR — Transportation · Status: effective
Cite this
- Citation
- 49 CFR 192.357, § 192.357 Customer meters and regulators: Installation, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257131
- Permanent ID
ys:prov:257131@1- SHA-256
aa7ed723816c91dc3c31f61da35f32461914f62e72a4892663499fab8da2d71f
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each meter and each regulator must be installed so as to minimize anticipated stresses upon the connecting piping and the meter.
(b) When close all-thread nipples are used, the wall thickness remaining after the threads are cut must meet the minimum wall thickness requirements of this part.
(c) Connections made of lead or other easily damaged material may not be used in the installation of meters or regulators.
(d) Each regulator that might release gas in its operation must be vented to the outside atmosphere.