49 CFR 192.381
§ 192.381 Service lines: Excess flow valve performance standards.
United States · 49 CFR — Transportation · Status: effective
Cite this
- Citation
- 49 CFR 192.381, § 192.381 Service lines: Excess flow valve performance standards, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257144
- Permanent ID
ys:prov:257144@1- SHA-256
7e13b4c91a00c275024d6852a5ffbb5d66a32bf60872f119e40de8f48ffe07c4
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Excess flow valves (EFVs) to be used on service lines that operate continuously throughout the year at a pressure not less than 10 p.s.i. (69 kPa) gage must be manufactured and tested by the manufacturer according to an industry specification, or the manufacturer's written specification, to ensure that each valve will:
(1) Function properly up to the maximum operating pressure at which the valve is rated;
(2) Function properly at all temperatures reasonably expected in the operating environment of the service line;
(3) At 10 p.s.i. (69 kPa) gage:
(i) Close at, or not more than 50 percent above, the rated closure flow rate specified by the manufacturer; and
(ii) Upon closure, reduce gas flow—
(A) For an excess flow valve designed to allow pressure to equalize across the valve, to no more than 5 percent of the manufacturer's specified closure flow rate, up to a maximum of 20 cubic feet per hour (0.57 cubic meters per hour); or
(B) For an excess flow valve designed to prevent equalization of pressure across the valve, to no more than 0.4 cubic feet per hour (.01 cubic meters per hour); and
(4) Not close when the pressure is less than the manufacturer's minimum specified operating pressure and the flow rate is below the manufacturer's minimum specified closure flow rate.
(b) An excess flow valve must meet the applicable requirements of Subparts B and D of this part.
(c) An operator must mark or otherwise identify the presence of an excess flow valve in the service line.
(d) An operator shall locate an excess flow valve as near as practical to the fitting connecting the service line to its source of gas supply.
(e) An operator should not install an excess flow valve on a service line where the operator has prior experience with contaminants in the gas stream, where these contaminants could be expected to cause the excess flow valve to malfunction or where the excess flow valve would interfere with necessary operation and maintenance activities on the service, such as blowing liquids from the line.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.