§ 192.463 External corrosion control: Cathodic protection.
United States · 49 CFR — Transportation · Status: effective
Cite this
- Citation
- 49 CFR 192.463, § 192.463 External corrosion control: Cathodic protection, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257155
- Permanent ID
ys:prov:257155@1- SHA-256
c5ba04233e1b7168bb89893e74d6ff200787cf03b2957d976b8b7a8eeb426f64
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each cathodic protection system required by this subpart must provide a level of cathodic protection that complies with one or more of the applicable criteria contained in appendix D of this part. If none of these criteria is applicable, the cathodic protection system must provide a level of cathodic protection at least equal to that provided by compliance with one or more of these criteria.
(b) If amphoteric metals are included in a buried or submerged pipeline containing a metal of different anodic potential—
(1) The amphoteric metals must be electrically isolated from the remainder of the pipeline and cathodically protected; or
(2) The entire buried or submerged pipeline must be cathodically protected at a cathodic potential that meets the requirements of appendix D of this part for amphoteric metals.
(c) The amount of cathodic protection must be controlled so as not to damage the protective coating or the pipe.