49 CFR 192.471
§ 192.471 External corrosion control: Test leads.
United States · 49 CFR — Transportation · Status: effective
Cite this
- Citation
- 49 CFR 192.471, § 192.471 External corrosion control: Test leads, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257159
- Permanent ID
ys:prov:257159@1- SHA-256
14010dd8cffb9ca834cc54bf88e425a74713c97e6917b2f579c587f38296c340
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each test lead wire must be connected to the pipeline so as to remain mechanically secure and electrically conductive.
(b) Each test lead wire must be attached to the pipeline so as to minimize stress concentration on the pipe.
(c) Each bared test lead wire and bared metallic area at point of connection to the pipeline must be coated with an electrical insulating material compatible with the pipe coating and the insulation on the wire.