yourstate.us
49 CFR 192.487

§ 192.487 Remedial measures: Distribution lines other than cast iron or ductile iron lines.

United States · 49 CFR — Transportation · Status: effective

Get this as JSONEmbed this
Cite this
Citation
49 CFR 192.487, § 192.487 Remedial measures: Distribution lines other than cast iron or ductile iron lines, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257169
Permanent ID
ys:prov:257169@1
SHA-256
ad8b0c06ff4d2eeffb2a2957d7ab3c01ffee5b3408b9626b263741fe958100b8

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) General corrosion. Except for cast iron or ductile iron pipe, each segment of generally corroded distribution line pipe with a remaining wall thickness less than that required for the MAOP of the pipeline, or a remaining wall thickness less than 30 percent of the nominal wall thickness, must be replaced. However, corroded pipe may be repaired by a method that reliable engineering tests and analyses show can permanently restore the serviceability of the pipe. Corrosion pitting so closely grouped as to affect the overall strength of the pipe is considered general corrosion for the purpose of this paragraph. (b) Localized corrosion pitting. Except for cast iron or ductile iron pipe, each segment of distribution line pipe with localized corrosion pitting to a degree where leakage might result must be replaced or repaired.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.