§ 192.736 Compressor stations: Gas detection.
United States · 49 CFR — Transportation · Status: effective
Cite this
- Citation
- 49 CFR 192.736, § 192.736 Compressor stations: Gas detection, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257239
- Permanent ID
ys:prov:257239@1- SHA-256
f6a545d41ce37cd7eb06a3f7e32cb40d312ab3b80c31a68333b6267c29674822
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Not later than September 16, 1996, each compressor building in a compressor station must have a fixed gas detection and alarm system, unless the building is—
(1) Constructed so that at least 50 percent of its upright side area is permanently open; or
(2) Located in an unattended field compressor station of 1,000 horsepower (746 kW) or less.
(b) Except when shutdown of the system is necessary for maintenance under paragraph (c) of this section, each gas detection and alarm system required by this section must—
(1) Continuously monitor the compressor building for a concentration of gas in air of not more than 25 percent of the lower explosive limit; and
(2) If that concentration of gas is detected, warn persons about to enter the building and persons inside the building of the danger.
(c) Each gas detection and alarm system required by this section must be maintained to function properly. The maintenance must include performance tests.