49 CFR 193.2615

§ 193.2615 Isolating and purging.

United States · 49 CFR — Transportation · Status: effective

Get this as JSONEmbed this
Cite this
Citation
49 CFR 193.2615, § 193.2615 Isolating and purging, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/257371
Permanent ID
ys:prov:257371@1
SHA-256
1e950180d46ab7f4f3bdbe67025ced8451d11461489b5e2a8f26e49eb0ed6442

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Before personnel begin maintenance activities on components handling flammable fluids which are isolated for maintenance, the component must be purged in accordance with a procedure which meets the requirements of “Purging Principles and Practices (incorporated by reference, see § 193.2013)”; unless the maintenance procedures under § 193.2605 provide that the activity can be safely performed without purging. (b) If the component or maintenance activity provides an ignition source, a technique in addition to isolation valves (such as removing spool pieces or valves and blank flanging the piping, or double block and bleed valving) must be used to ensure that the work area is free of flammable fluids.

Legislative history