§ 236.552 Insulation resistance; requirement.

United States · 49 CFR — Transportation · Status: effective

Get this as JSONEmbed this
Cite this
Citation
49 CFR 236.552, § 236.552 Insulation resistance; requirement, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/259078
Permanent ID
ys:prov:259078@1
SHA-256
034e0ae6d501fd56ddd5b2b01ca89b4cdcb8d2539723394d0a42078e7a82cf2b

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

When periodic test prescribed in § 236.588 is performed, insulation resistance between wiring and ground of continuous inductive automatic cab signal system, automatic train control system, or automatic train stop system shall be not less than one megohm, and that of an intermittent inductive automatic train stop system, not less than 250,000 ohms. Insulation resistance values between periodic tests shall be not less than 250,000 ohms for a continuous inductive automatic cab signal system, automatic train control system, or automatic train stop system, and 20,000 ohms for an intermittent inductive automatic train stop system.