yourstate.us
10 CFR 36.83

§ 36.83 Reports.

United States · 10 CFR — Energy · Status: effective

Get this as JSONEmbed this
Cite this
Citation
10 CFR 36.83, § 36.83 Reports, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/37091
Permanent ID
ys:prov:37091@1
SHA-256
cd4204624508929905b4be5856306da666da67af702b70ba59b4fc11c6d7a0a3

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) In addition to the reporting requirements in other parts of NRC regulations, the licensee shall report the following events if not reported under other parts of NRC regulations: (1) Source stuck in an unshielded position. (2) Any fire or explosion in a radiation room. (3) Damage to the source racks. (4) Failure of the cable or drive mechanism used to move the source racks. (5) Inoperability of the access control system. (6) Detection of radiation source by the product exit monitor. (7) Detection of radioactive contamination attributable to licensed radioactive material. (8) Structural damage to the pool liner or walls. (9) Abnormal water loss or leakage from the source storage pool. (10) Pool water conductivity exceeding 100 microsiemens per centimeter. (b) The report must include a telephone report within 24 hours as described in § 30.50(c)(1), and a written report within 30 days as described in § 30.50(c)(2).

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.