§ 434.515 Receptacles.
United States · 10 CFR — Energy · Status: effective
Cite this
- Citation
- 10 CFR 434.515, § 434.515 Receptacles, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/39696
- Permanent ID
ys:prov:39696@1- SHA-256
5f6a72801bce8260799de0efa8a4d18a3b66135f78a8926c2f4902f3b6afc305
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
515.1 Receptacle loads and profiles are default assumptions. The same assumptions shall be made in calculating Design Energy Consumption as were used in calculating the Energy Cost Budget.
515.2 Receptacle loads include all general service loads that are typical in a building. These loads exclude any process electrical usage and HVAC primary or auxiliary electrical usage. Table 515.2, Receptacle Power Densities, establishes the density, in W/ft 2, to be used for each building type. The receptacle energy profiles shall be the same as the lighting energy profiles in Table 513.2.b. This profile establishes the percentage of the receptacle load that is switched on by hour of the day and by building type.
Table 515.2—Receptacle Power Densities