§ 29.1187 Drainage and ventilation of fire zones.
United States · 14 CFR — Aeronautics and Space · Status: effective
Cite this
- Citation
- 14 CFR 29.1187, § 29.1187 Drainage and ventilation of fire zones, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/54906
- Permanent ID
ys:prov:54906@1- SHA-256
30d0b11215067137874214f431d64fc78560fb9e68e39dbe2dada445d6493e01
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) There must be complete drainage of each part of each designated fire zone to minimize the hazards resulting from failure or malfunction of any component containing flammable fluids. The drainage means must be—
(1) Effective under conditions expected to prevail when drainage is needed; and
(2) Arranged so that no discharged fluid will cause an additional fire hazard.
(b) Each designated fire zone must be ventilated to prevent the accumulation of flammable vapors.
(c) No ventilation opening may be where it would allow the entry of flammable fluids, vapors, or flame from other zones.
(d) Ventilation means must be arranged so that no discharged vapors will cause an additional fire hazard.
(e) For category A rotorcraft, there must be means to allow the crew to shut off the sources of forced ventilation in any fire zone (other than the engine power section of the powerplant compartment) unless the amount of extinguishing agent and the rate of discharge are based on the maximum airflow through that zone.